How to Interpret Your DGA Report and Choose the Right Oil Purification Schedule?
The Dissolved Gas Analysis (DGA) test is like a “blood test” for your transformer. With this diagnostic, you can identify internal faults before they result in costly equipment failures that are costly in more ways than one. But receiving the analysis results from the lab is just one step toward ensuring safe operation of your electrical systems. Deciphering those figures in parts per million (ppm) is quite an undertaking on its own.
If the recent analysis indicated increased levels of dissolved gases such as Hydrogen (H2) or Acetylene (C2H2), then replacing the oil in your transformers won’t be your only option—and not necessarily the cheapest one. High-vacuum insulation oil purification will help you bring back the values of oil parameters. The following content will show you how to read your DGA results and decide exactly when to schedule your next oil purification.

Key DGA Gases & What They Whisper About Your Transformer
The breakdown of the transformer oil and paper due to heat and electrical stress is achieved through the formation of distinct gases. The analysis of the particular mixture of gases in terms of concentrations will help detect any faults that may cause tank failure.

The table below shows some important gases for analysis in your laboratory DGA report:
| Fault Gas | Main Cause and Indication | Severity Level | Risk and Recommended Action |
| Hydrogen (H2) | Partial discharge, corona, or low-intensity sparking. | Low to Medium | Indicates early-stage electrical stress. Monitor trend. |
| Methane and Ethane (CH4 / C2H6) | Low-to-medium temperature thermal faults. | Medium | Points to localized overheating of oil or magnetic joints. |
| Ethylene (C2H4) | High-temperature thermal faults (greater than 700 deg C). | High | Severe localized overheating, often near internal connections. |
| Acetylene (C2H2) | High-energy electrical arcing or sustained short circuits. | CRITICAL | Extreme risk of explosion. Requires immediate shutdown. |
| Carbon Monoxide (CO / CO2) | Thermal decomposition of solid paper insulation. | High | Accelerated aging of the transformer winding insulation. |
The 3-Step Decision Matrix: When to Schedule Oil Purification
In order to facilitate your decision immediately, we have condensed the international standards such as IEEE C57.104 and IEC 60599 into a useful 3-tiered matrix form. Simply compare your most recent lab numbers to find out which steps need to be taken immediately.
Level 1 – Normal/ Acceptable
In case all combustible fault gases fall well below safety margins (i.e., H2 is less than 100 ppm and C2H2 is absolute zero), you can rest assured that your transformer is in great condition. The internal environment is stable, and no threats exist.
What You Need To Do Next: Follow the schedule. It is important to remember that even though the oil may be considered healthy in the DGA test, the prevention of vacuum oil filtration should take place every 6 to 12 months.
Level 2: Early Warning Indicator
At this stage, your transformer sends you a warning signal about an issue. What you will notice in the test results is Hydrogen being on the rise to a level between 100 and 700 ppm, or rapid growth in Methane (CH4) and carbon dioxide (CO/CO2). The readings are still far from critical, but consistent month-to-month growth indicates the development of a low-level thermal or electrical fault inside the tank.
Your Actions: Do not neglect the growing trends. You have to arrange vacuum oil purification in the next 1 to 3 months. It will isolate the fault in its early stages, remove the dissolved gases, and protect the solid paper insulation against premature ageing.
Level 3: Imminent Threat
This is an urgent situation. The presence of Acetylene (C2H2) above the 2 to 3 ppm level and/or Total Dissolved Combustible Gases (TDCG) above 1500 ppm indicates imminent high-energy arcing and excessive localized overheating. Operation of the transformer under such conditions poses a risk of catastrophic explosion and system collapse.
What To Do: Act immediately. Shutdown the transformer if your schedule permits it. In any case, you need to connect a highly efficient two-stage vacuum transformer oil purification system. This will allow you to aggressively remove harmful gases, decrease moisture content, and filter out carbon soot particles.
How the Right Oil Purifier Fixes the DGA Issues
Most people believe that because of high DGA values, it means that the oil has been damaged and needs to be completely changed. Actually, a good quality insulation oil purifier solves the problem and restores the properties of the oil for a much lower price than buying new oil.


- High Vacuum Degassing: Industrial transformer oil treatment machines operate using two-stage vacuum chambers. The process of boiling off dissolved fault gases such as hydrogen, methane, and even very dangerous acetylene gas takes place because of low pressure and oil heating.
- Dehydration: A lot of CO and CO2 in the oil usually means that wet paper insulation starts degrading. The moisture level is reduced to less than 5 ppm by a vacuum purifier and stops the vicious cycle of moisture-induced formation of acids and deterioration of paper.
- Particulate Filtration: Electrical arcing produces carbon dust or soot particles. Multi-stage filters remove those particles from the oil and restore oil dielectric breakdown voltage to acceptable limits (> 60 kV or 70 kV).
Actionable Next Step
Don’t wait for an active warning flag on your DGA report to turn into a grid failure. Review your most recent lab results today. If you notice rising ppm levels or are due for a preventative clean, matching your fluid with the right high-vacuum filtration equipment is your fastest path to compliance.
Have questions about your specific DGA readings? Contact our technical engineering team to share your report, and let us recommend the exact single-stage or double-stage oil purifier configuration required to safeguard your assets.